NVIDIA NCA-APC exam · AI Power and Cooling · Official objectives · Original practice content

Free NCA-APC Cooling and Mechanical Infrastructure Awareness Practice Questions

Reviewed by the FlashGenius certification content team · Last updated: November 24, 2026 · Aligned to NVIDIA's published NCA-APC exam topics and weights

The Cooling and Mechanical Infrastructure Awareness domain is 17% of the NVIDIA NCA-APC (AI Power and Cooling) exam and covers the heat path, air versus direct liquid cooling, CDUs, manifolds, pumps and valves, water quality, leaks and condensation, and cooling escalation. Review each answer and explanation as you practice.

The NCA-APC exam has 50 multiple-choice questions in 1 hour. It costs $125, results are pass or fail, and the certification is valid for 2 years. It needs no calculations and no AI background.

Take the 10-question NCA-APC quick-start test · NCA-APC cheat sheet · Create a free account

What Cooling and Mechanical Infrastructure Awareness covers on the NCA-APC exam

This domain is 17% of the NCA-APC exam (about 9 questions in a 50-question mock). NVIDIA's objectives include:

How to study Cooling and Mechanical Infrastructure Awareness

NCA-APC Cooling and Mechanical Infrastructure Awareness sample questions with answers

Cooling and Mechanical Infrastructure Awareness

Sample question 1

A site orientation slide shows the two liquid loops that serve a liquid-cooled AI hall:

Technology cooling system (TCS): cold plates <-> rack manifolds <-> CDU
Facility water system (FWS):    CDU <-> central plant <-> dry coolers

Which equipment does the facility water system (FWS) connect?

  1. The cold plates, the rack manifolds and the CDUs
  2. The cold plates, the CDUs and the dry coolers
  3. The CDUs, the central plant and the outdoor dry coolers
  4. The rack manifolds, the central plant and the dry coolers
Show correct answer and explanation

Correct answer: C. The CDUs, the central plant and the outdoor dry coolers

C is correct because the FWS picks up heat at the CDU heat exchangers and carries it through the central plant to the dry coolers, which reject it outdoors. A is incorrect because that is the technology cooling system, the loop on the rack side of the CDU. B is incorrect because the two loops are kept separate at the CDU; rack coolant never flows out to the dry coolers. D is incorrect because the manifolds stay on the technology cooling system, which ends at the CDU.

Cooling and Mechanical Infrastructure Awareness

Sample question 2

A hall's facility water loop serves both CRAHs and CDUs. Where does each of them pick up the heat that it passes into that loop?

  1. CRAHs take it from room air; CDUs take it from rack coolant
  2. Both take it from rack coolant, one for each half of the row
  3. Both take it from room air, at different points in the hall
  4. CRAHs take it from outdoor air; CDUs take it from the chillers
Show correct answer and explanation

Correct answer: A. CRAHs take it from room air; CDUs take it from rack coolant

A is correct because a CRAH coil cools the warm room air, while a CDU heat exchanger cools the coolant returning from the cold plates; both hand that heat to the facility water. B is incorrect because a CRAH has an air coil and fans; it cools room air, not rack coolant. C is incorrect because a CDU is a liquid-to-liquid unit; it does not cool room air. D is incorrect because CRAHs work on the air inside the hall, and the chillers are downstream of the CDUs, not a heat source for them.

Cooling and Mechanical Infrastructure Awareness

Sample question 3

In a direct liquid cooled GPU rack, at which component does heat from the processors first pass into the liquid loop?

  1. The rack manifolds that feed each tray
  2. The heat exchanger inside the CDU
  3. The cold plates mounted on the processors
  4. The facility water piping in the gallery
Show correct answer and explanation

Correct answer: C. The cold plates mounted on the processors

C is correct because cold plates sit directly on the GPUs and CPUs, so they are where processor heat first moves into the coolant. A is incorrect because the manifolds distribute and collect coolant; the heat has already entered the liquid at the cold plates. B is incorrect because the CDU heat exchanger is further along the path, where heat leaves the rack coolant for the facility water. D is incorrect because facility water picks up heat at the CDU, after the rack coolant has carried it away from the processors.

Cooling and Mechanical Infrastructure Awareness

Sample question 4

A plant diagram reads: IT racks -> CRAH -> chilled water -> chiller -> condenser water -> cooling tower. Which item in this chain releases the heat to the outdoor air?

  1. The chiller
  2. The condenser water loop
  3. The CRAH
  4. The cooling tower
Show correct answer and explanation

Correct answer: D. The cooling tower

D is correct because the cooling tower is the last step in the chain, rejecting heat to the atmosphere by evaporating part of the condenser water. A is incorrect because the chiller moves heat from the chilled water into the condenser water; it does not release it outdoors here. B is incorrect because the condenser water only carries heat from the chiller to the tower; the tower releases it. C is incorrect because the CRAH is the first step, moving heat from room air into the chilled water.

Cooling and Mechanical Infrastructure Awareness

Sample question 5

On a mild spring night, a controls technician reviews this central plant screen:

Central plant mode       WATERSIDE ECONOMIZER
Chiller 1                OFF
Chiller 2                OFF
Plate heat exchanger     IN SERVICE
Cooling towers           RUNNING
Chilled water supply     15.2 C   (setpoint 15.0 C)

How is heat MOST likely leaving the chilled water loop?

  1. Through the chillers, which are carrying the load in standby
  2. Through the plate heat exchanger into the cooling tower water
  3. Through the CDUs, which pass it into the rack coolant
  4. Through the CRAHs, which release it into the hall air
Show correct answer and explanation

Correct answer: B. Through the plate heat exchanger into the cooling tower water

B is correct because in waterside economizer mode a plate heat exchanger lets cooling tower water cool the chilled water directly, so the chillers can stay off. A is incorrect because both chillers are shown OFF; in economizer mode the heat exchanger bypasses them. C is incorrect because CDUs move heat from the rack coolant into facility water, not the other way round. D is incorrect because CRAHs move heat from room air into the chilled water, the opposite direction.

Cooling and Mechanical Infrastructure Awareness

Sample question 6

A retrofit site keeps its open cooling tower water apart from its closed facility water loop by placing a plate heat exchanger between them. On the heat path from the racks to the outdoors, what happens at that heat exchanger?

  1. Heat moves from the tower water back into the facility loop
  2. The heat exchanger releases the heat straight to outdoor air
  3. Tower water flows into the closed loop to replace the warm water
  4. Heat moves into the tower water; the two waters do not mix
Show correct answer and explanation

Correct answer: D. Heat moves into the tower water; the two waters do not mix

D is correct because heat passes through the plates from the closed facility loop to the tower water, while the open tower water stays out of the closed loop. A is incorrect because heat moves from the warmer facility water to the cooler tower water, toward the outdoors. B is incorrect because a plate heat exchanger is water to water; the cooling tower is what releases the heat outdoors. C is incorrect because the heat exchanger exists to keep the open tower water out of the closed loop.

Cooling and Mechanical Infrastructure Awareness

Sample question 7

A visiting inspector asks a facilities technician whether the site evaporates water to reject heat. The posted heat-path diagram reads: cold plates -> CDU -> facility water -> chiller -> dry coolers. What does the diagram support?

  1. Heat leaves through a cooling tower that follows the dry coolers
  2. Heat leaves through dry coolers, with no evaporative step shown
  3. Heat leaves through the chiller, which evaporates water outdoors
  4. Heat leaves the rack coolant directly at the dry coolers
Show correct answer and explanation

Correct answer: B. Heat leaves through dry coolers, with no evaporative step shown

B is correct because dry coolers pass the warm water through finned coils while fans move outdoor air across them, so heat is released without evaporating water. A is incorrect because no cooling tower appears in the diagram; reading in equipment that is not shown goes beyond the information. C is incorrect because a chiller moves heat between water loops; in this diagram the dry coolers are the outdoor step. D is incorrect because the rack coolant stays on the rack side of the CDU; facility water carries the heat onward.

Cooling and Mechanical Infrastructure Awareness

Sample question 8

During commissioning week, an apprentice pipefitter asks which way heat moves inside a CDU's heat exchanger while the GPU racks are running. What is the correct answer?

  1. From the facility water into the air through the CDU fans
  2. From the rack coolant into the air around the CDU cabinet
  3. From the rack coolant straight into the chiller refrigerant
  4. From the rack coolant into the facility water
Show correct answer and explanation

Correct answer: D. From the rack coolant into the facility water

D is correct because the CDU transfers heat from the technology cooling loop to the facility water, which carries it away to the plant. A is incorrect because the facility water carries heat to the central plant and heat rejection equipment, not into the hall. B is incorrect because a CDU uses a liquid-to-liquid heat exchanger; it hands heat to water, not to the room. C is incorrect because the rack coolant never leaves the CDU; facility water carries the heat on toward any chillers.

Cooling and Mechanical Infrastructure Awareness

Sample question 9

In a retrofit of an existing data center, the GC superintendent asks an electrician whether the new CDUs will reject heat into the old chilled water system or into new dry coolers. Where should the answer come from?

  1. The electrician's judgment after walking the existing plant
  2. The electrical one-line diagram for the new CDU feeders
  3. The approved mechanical flow diagrams for the retrofit
  4. The original as-built drawings of the existing plant
Show correct answer and explanation

Correct answer: C. The approved mechanical flow diagrams for the retrofit

C is correct because how the new loops connect to heat rejection is set by the mechanical design, so the answer comes from those documents or the mechanical contractor, not a guess. A is incorrect because a walk shows existing equipment, not what the retrofit design connects, and the design belongs to another trade. B is incorrect because the one-line shows how the CDUs are powered, not where their heat goes. D is incorrect because as-built drawings show the old plant as it was built, not what the retrofit design connects to it.

Cooling and Mechanical Infrastructure Awareness

Sample question 10

A colocation retrofit adds rear door heat exchangers to existing air-cooled racks. Where does the server heat move from the air into water?

  1. At the cooling towers in the central plant
  2. At the CRAH coils at the end of each row
  3. At the cold plates on each processor
  4. At the coil in each rack's rear door
Show correct answer and explanation

Correct answer: D. At the coil in each rack's rear door

D is correct because the server fans still push heat into the air, and the water coil in the rear door picks it up before the air re-enters the room. A is incorrect because cooling towers release heat outdoors at the end of the path; they do not take heat from rack air. B is incorrect because the rear door coil captures the heat at the rack; CRAHs handle whatever heat remains in the room. C is incorrect because the racks are air cooled; there are no cold plates in this retrofit.