NVIDIA NCA-APC exam · AI Power and Cooling · Official objectives · Original practice content

Free NCA-APC Operations and Maintenance Awareness Practice Questions

Reviewed by the FlashGenius certification content team · Last updated: November 24, 2026 · Aligned to NVIDIA's published NCA-APC exam topics and weights

The Operations and Maintenance Awareness domain is 15% of the NVIDIA NCA-APC (AI Power and Cooling) exam and covers dashboards, alarms and rounds, readings against limits, SOPs and MOPs, cross-system symptoms, shift handoffs, PUE and WUE, and preventive maintenance. Review each answer and explanation as you practice.

The NCA-APC exam has 50 multiple-choice questions in 1 hour. It costs $125, results are pass or fail, and the certification is valid for 2 years. It needs no calculations and no AI background.

Take the 10-question NCA-APC quick-start test · NCA-APC cheat sheet · Create a free account

What Operations and Maintenance Awareness covers on the NCA-APC exam

This domain is 15% of the NCA-APC exam (about 7 questions in a 50-question mock). NVIDIA's objectives include:

How to study Operations and Maintenance Awareness

NCA-APC Operations and Maintenance Awareness sample questions with answers

Operations and Maintenance Awareness

Sample question 1

A new facilities technician asks why the BMS screen offers a trend view for each point when the current reading is already displayed. What does a trend view show that a single reading does not?

  1. How the value has changed over time, including slow drift
  2. The cause of the alarm that is active on that point
  3. Which technician last changed the setpoint for that point
  4. The design limit that the equipment manufacturer has set
Show correct answer and explanation

Correct answer: A. How the value has changed over time, including slow drift

A is correct because a trend plots readings over a period, so a gradual rise or a repeating swing becomes visible even while each individual reading still looks acceptable. B is incorrect because a trend shows what the value did over time; finding the cause still takes investigation by the system owner. C is incorrect because who changed a setting is recorded in the change or audit log, not in a trend of the measured value. D is incorrect because limits come from the procedure or equipment data; a trend shows the history of the measured value.

Operations and Maintenance Awareness

Sample question 2

A site already monitors its CDUs, pumps and electrical rooms through the BMS. Why does the operations team still send technicians on scheduled walk-through rounds?

  1. To replace the BMS readings with handwritten values for the records
  2. To adjust each setpoint by hand so the equipment stays near its target
  3. To find conditions that sensors do not measure, such as drips or odors
  4. To reset alarms locally so they do not appear on the BMS screen
Show correct answer and explanation

Correct answer: C. To find conditions that sensors do not measure, such as drips or odors

C is correct because rounds let a person see, hear and smell conditions that no sensor covers, such as a weeping fitting, an unusual noise, damaged insulation or a blocked access path. A is incorrect because rounds add to the BMS data; they do not replace the monitored readings in the records. B is incorrect because setpoint changes are controlled changes made by authorized staff, not a routine task on a walk-through. D is incorrect because alarms are there to be seen and handled; clearing them locally on rounds would hide conditions from operators.

Operations and Maintenance Awareness

Sample question 3

What is the PRIMARY purpose of setting an alarm threshold on a monitored point such as a CDU supply temperature?

  1. To alert operators when the value leaves its expected range
  2. To stop the equipment automatically whenever the value changes
  3. To record each reading so the trend can be reviewed later on
  4. To keep the value from rising above the threshold that was set
Show correct answer and explanation

Correct answer: A. To alert operators when the value leaves its expected range

A is correct because an alarm threshold turns a reading into a prompt for action, telling operators that the value has moved outside its expected range so the response procedure can begin. B is incorrect because most alarms notify people; any automatic action is a separate, deliberately configured response. C is incorrect because recording readings is the job of the trend or historian; the alarm threshold is about prompting a response. D is incorrect because an alarm reports a condition; it does not control the process or hold the value down.

Operations and Maintenance Awareness

Sample question 4

During a night shift, a technician acknowledges a high-temperature alarm for CRAH-4 on the BMS, and the alarm changes from flashing to steady. What does the acknowledgment MOST likely mean?

  1. The high temperature has returned to normal and the alarm is closed
  2. Someone has seen the alarm, but the condition may still be present
  3. The BMS has fixed the problem by changing the CRAH-4 setpoint
  4. The alarm was false and has been removed from the alarm history
Show correct answer and explanation

Correct answer: B. Someone has seen the alarm, but the condition may still be present

B is correct because acknowledging records that an operator has seen the alarm; the alarm stays active until the measured condition returns to normal, so the response still has to continue. A is incorrect because an alarm clears when the condition clears; acknowledging it only shows it has been seen. C is incorrect because acknowledging an alarm does not change any equipment setting. D is incorrect because acknowledging does not judge the alarm false, and alarm history is kept for later review.

Operations and Maintenance Awareness

Sample question 5

At 15:20 a shift lead checks the hall 2 dashboard and sees this tile:

CDU-6   Hall 2
Status:        Running
Supply temp:   29.4 C
Data:          COMM LOSS   last update 12:05

What does the tile support?

  1. The 29.4 C supply temperature is the reading at 15:20
  2. CDU-6 has failed and its racks are losing cooling at this moment
  3. CDU-6 is running normally, since its status still reads Running
  4. The data is more than three hours old, so CDU-6's state now is unknown
Show correct answer and explanation

Correct answer: D. The data is more than three hours old, so CDU-6's state now is unknown

D is correct because the communication-loss flag and the 12:05 timestamp show the tile is frozen at old values, so it cannot confirm what CDU-6 is doing now and the data loss itself needs reporting. A is incorrect because that value was last updated at 12:05, more than three hours earlier. B is incorrect because lost data is not proof of a failed unit; the tile simply cannot show the current condition. C is incorrect because the Running status is from 12:05; a stale tile says nothing about the current state.

Operations and Maintenance Awareness

Sample question 6

A retrofit adds temperature sensors at the inlet of each AI rack and shows them on the DCIM floor map. Why is this MORE useful than relying on the existing room temperature sensors?

  1. A room average can hide a hot spot at one dense rack
  2. Room sensors stop working once liquid-cooled racks are installed
  3. Rack-inlet sensors let the DCIM raise the room setpoint by itself
  4. Rack-inlet sensors measure the rack's power use as well as heat
Show correct answer and explanation

Correct answer: A. A room average can hide a hot spot at one dense rack

A is correct because rack-inlet sensors show the air each rack actually receives, so a local hot spot or recirculation at a dense rack is visible even when the room average looks normal. B is incorrect because room sensors keep working; they just do not show conditions at each rack inlet. C is incorrect because the sensors provide visibility; setpoint changes remain controlled decisions by authorized staff. D is incorrect because a temperature sensor measures temperature; power is measured by meters on the electrical path.

Operations and Maintenance Awareness

Sample question 7

The BMS alarm history shows a CRAH-2 high-temperature alarm at 02:10 that cleared at 02:25. The day-shift lead wants to know whether anyone went to the unit overnight and what they found. Where is this MOST likely recorded?

  1. In the CRAH-2 supply air trend, which shows the overnight readings
  2. In the shift log, where staff note what they checked and found
  3. In the alarm history, which stores each visit made to the unit
  4. In the DCIM floor map, which shows the status of each unit in the hall
Show correct answer and explanation

Correct answer: B. In the shift log, where staff note what they checked and found

B is correct because a shift log records the human side of an event, such as who went to the unit, what they saw and who they called, which monitoring data does not capture. A is incorrect because a trend shows how the measured value changed; it says nothing about who went to the unit or what they saw. C is incorrect because alarm history records when alarms started, were acknowledged and cleared; it does not record field visits or findings. D is incorrect because the floor map shows current status, not a record of what people did during the night.

Operations and Maintenance Awareness

Sample question 8

At the start of the day shift, a facilities supervisor notices that a high-differential-pressure alarm on a CDU filter came in and cleared three times overnight. Why is the event log worth reviewing even though no alarm is active now?

  1. The log matters mainly while an alarm is still active on the screen
  2. Reviewing the log resets the alarm counters so the filter is retested
  3. Repeated alarms that clear by themselves can show a developing problem
  4. A cleared alarm means the filter was replaced during the night shift
Show correct answer and explanation

Correct answer: C. Repeated alarms that clear by themselves can show a developing problem

C is correct because the log shows when each alarm occurred and how long it lasted, and a pattern of alarms that clear on their own can point to a condition that is getting worse. A is incorrect because logs are most useful for reviewing events after the fact, including alarms that have already cleared. B is incorrect because reading a log changes nothing on the equipment or its alarms. D is incorrect because an alarm clearing means the value returned to range; it does not show that any work was done.

Operations and Maintenance Awareness

Sample question 9

The DCIM floor map legend reads: green = normal, amber = warning threshold reached, red = alarm threshold reached. A controls technician on a site walk sees rack 31 shown amber. What does the display indicate?

  1. Rack 31 has reached its warning level but not its alarm level
  2. Rack 31 has exceeded its alarm limit and needs emergency action
  3. Rack 31 is normal, because amber marks racks under maintenance
  4. Rack 31 has lost communication with the DCIM monitoring system
Show correct answer and explanation

Correct answer: A. Rack 31 has reached its warning level but not its alarm level

A is correct because the legend defines amber as the warning threshold, which sits before the alarm threshold, so the rack has moved toward its limit without reaching the alarm level. B is incorrect because the legend assigns the alarm threshold to red, not amber. C is incorrect because the legend defines amber as a warning threshold and lists no maintenance state. D is incorrect because the legend does not use amber for communication loss; it marks a warning threshold.

Operations and Maintenance Awareness

Sample question 10

The site alarm procedure says to respond to Priority 1 alarms first. A technician starting the night shift sees this alarm list:

Time   Pri  Point                              State
22:41  3    Hall 1 door 4 held open            Active, unacknowledged
22:38  2    CDU-2 filter diff pressure high    Active, unacknowledged
21:57  1    UPS-3 on bypass                    Active, acknowledged
21:50  1    CRAH-2 fan fault                   Cleared

Which alarm should the technician address FIRST?

  1. UPS-3 on bypass, since it is Priority 1 and still active
  2. Hall 1 door 4 held open, since it is the newest alarm
  3. CDU-2 filter differential pressure, since it is unacknowledged
  4. CRAH-2 fan fault, since it was the first Priority 1 alarm logged
Show correct answer and explanation

Correct answer: A. UPS-3 on bypass, since it is Priority 1 and still active

A is correct because the procedure ranks Priority 1 first, and the UPS-3 alarm is still active; acknowledging it earlier showed it was seen but did not resolve it. B is incorrect because the procedure ranks by priority, not by time, and the door alarm is Priority 3. C is incorrect because an unacknowledged Priority 2 alarm still ranks below an active Priority 1 alarm under the procedure. D is incorrect because the CRAH-2 alarm has cleared, while the UPS-3 Priority 1 alarm is still active.